Does SF6 switchgear need periodic leak checks, and how often?

Article 5(1) of Regulation (EU) 2024/573 requires leak checks on equipment with 5 tonnes of CO2 equivalent or more, but switchgear is exempt where it has a tested leakage rate below 0,1 percent a year and is labelled so, or a pressure or density monitor with an automatic alert, or less than 6 kg of gas. Otherwise Article 5(6) sets the frequency: every 12 months below 50 t CO2 equivalent, every 6 months from 50 to 500 t, every 3 months from 500 t (24, 12 and 6 months with a leakage detection system). One kilogram of SF6 is 24,3 t CO2 equivalent (GWP 24 300).

What the Act Says

Article 5(1)
The three switchgear conditions that remove the leak-check duty.
Article 5(6)
The check frequency by CO2 equivalent.
Annex I
SF6 has a GWP of 24 300: 4 kg is 97,2 t CO2 equivalent, 30 kg is 729 t.
Article 7
Records of checks are kept for at least five years.